HydroTOUCH Soft Start Pump Controller
The HydroTOUCH Soft Start range of pump controllers is a market leading, second-generation multi-pump controller designed to operate up to 12 pumps. It features a wide range of advanced control options and a highly flexible array or input and output signals, both digital and analogue. Incorporating an easy set-up wizard and a user-friendly touch screen, operation of these sophisticated controllers is a breeze!
HydroTOUCH controllers have been designed for four different control operations - Pressure, Level, Flow and Temperature and are highly customisable to suit your specific application.
Enclosure
- IP56 rated, powder-coated mild steel enclosure with inner door and removable gland plate
Protection
- Pad-lockable mains power isolator switch
- Circuit breaker protected low voltage control and input circuitry
- Individual pump isolation
- Contactor and thermal overload protection of pump motors
- Din rail-mounted terminal connections
Control & Interface
- HydroTOUCH colour touch screen HMI (See interface features)
- HydroTOUCH PCB control module
- Visual (strobe) and mutable audible (buzzer) alarms
- Soft starter per pump with adjustable soft start and stop (Soft Start version)
Inputs
- Single phase (230Vac) or three phase (400Vac) power supply
- 2x Analogue 4-20mA inputs for level, pressure or temperature transducers
- Up to 5x digital 24Vdc inputs for float or pressure switches or thermostats
- Digital pulse input for flow meter
- Standard terminal setup: Primary and secondary level transducers, backup low and high-level floats, and flow input
- Thermal switch inputs per pump (three phase only)
Outputs
- 1-12 Soft Start Supply Outlets for Pumps
- BMS volt-free output for common fault (additional available upon request)
- 2x Analogue 4-20mA BMS outputs for analogue readings
- Output for solenoid valve available upon request
- Modbus RTU Serial RS485 connections for SCADA
Function Features
- Multi Pump Control - Control of up to 12 pumps in any number of duty, duty assist and standby pump configurations
- Pump Limiting - For limiting max flow or power requirements
- Duty Sharing and Alternation - Adjustable duty change period and bumpless transfer
- Pump Staging and Destaging - Additional pumps are staged into operation to maintain setpoint and destaged when no longer required
- Staggered Pump Start and Stop - Prevents excessive current draw and reduces water surge or hammer
- Manual Pump Control - Pump manual mode with ability to override system protections for 15 mins, before reverting back to auto mode
- System Types - Level, pressure or temperature control modes
- Control Directions - For emptying or filling a tank
- Level Control Mode - Controlled by 4-20mA level transducer and optional backup high- and low-level float switches
- Maintain Minimum Level - Ensures minimum tank level is maintained
- Well Wash Valve Control - When the system has pumped down to setpoint and the pumps have stopped, the system will open the well wash valve for 5 minutes every 24 hours
- Tank Top Up Valve Control - Tops up tank with mains water when normal inflow of rain or treated water into tank does not keep up with demand (available upon request)
- Auxiliary Tank Level Monitoring - Using additional level transducer in auxiliary tank, instead of backup transducer
- UV Lamp Control - Optional UV lamp control for installations that require UV filtering, with adjustable modes
Fault Protection
- Protection Modes - Most protections feature adjustable modes including alarm (alarm only), lockout (alarm and pump shut-down) and inhibit (pump shut-down, no alarm)
- High and Low Level, Pressure or Temperature Protection - Alarm and/or shutdown on high and low level, pressure or temperature depending on the system type, low pressure and flow feature auto restart attempts
- Medium Level Protection - Provides an additional level alarm before the high or low level is reached
- Auxiliary Tank Level Protection - High- and low-level protection from floats or level transducer in auxiliary tank
- Auxiliary High & Low Temp Protection - If using additional temperature device instead of backup transducer (specific to temperature mode)
- Pump Anti-seize Protection - Runs pumps periodically during low use to prevent seizing
- Maximum Flow Protection - Activates after pumps run at max flow for 30mins, protecting the system in the event of a burst pipe
- Pump Cycle Protection - Activates if system goes to sleep but wakes up within 5 seconds, 10 times in a row, due to a faulty non-return valve or similar fault preventing the system from maintaining pressure
- Low Flow Protection - Alarms and/or shuts down pump or system if a pump is running but there is no flow for 30 seconds, with automatic restart attempts before activating a lockout
- Analogue Fault Protection - Activates faults if analogue inputs fail
- Transducer Redundancy - Switches to backup transducer if primary transducer fails (if using backup transducer)
- Transducer Discrepancy - If difference between primary and secondary transducers exceeds a certain amount, system will use the most appropriate input relative to the setpoint to protect system from overshooting
- Pump Overload Protection - Shuts down pumps on overload, with automatic duty alternation
- Pump Thermal Switch Protection - For three phase pumps
- Filter Blocked Protection - Protects the system when filters are blocked or faulty
- UV Fault Protection - Protects the system when UV filters are faulty
Interface Features
- Main screen with system and pump status, active faults, analogue values
- Individual pump monitoring screen with status, run hours, number of starts, manual control with ability to override system lockouts
- Graphical overview screen for monitoring overall system operation
- Alarm screen with date and time stamped faults
- Logged data screen with water usage graph, trend graphs for pressure, level and flow, pump run timers and system event counters
- System diagnostics screen for easy fault finding, pump rotation testing
- User friendly setup wizard for easy commissioning
- Advanced parameter adjustment
Code | No of Pumps | Phase/Voltage | SS Options |
FPC-43141-S | Single | 1 Phase / 230 Vac | -S4.0 to -S90 |
FPC-43143-S | Single | 3 Phase / 400 Vac | -S4.0 to -S90 |
FPC-43241-S | Dual | 1 Phase / 230 Vac | -S4.0 to -S90 |
FPC-43243-S | Dual | 3 Phase / 400 Vac | -S4.0 to -S90 |
FPC-43341-S | Triplex | 1 Phase / 230 Vac | -S4.0 to -S90 |
FPC-43343-S | Triplex | 3 Phase / 400 Vac | -S4.0 to -S90 |
FPC-43441-S | Quad | 1 Phase / 230 Vac | -S4.0 to -S90 |
FPC-43443-S | Quad | 3 Phase / 400 Vac | -S4.0 to -S90 |
Optional Modifications
- Additional BMS volt-free outputs
- With ME-Link SMS Module for SMS alarm/status messaging
- With rain/mains changeover control module and 12Vdc pulse latching solenoid valve
- Generator input socket and manual changeover switch or automatic changeover
- Output for normally closed tank top-up or well wash valve
- Individual pump RCD protection
- 316 stainless steel enclosure
- Free-standing enclosure with plinth
- Separate compartments for power authority meter
- Battery backup high-level alarm
- Conductivity relays and probe inputs
- Modbus TCP gateway with an ethernet port