HydroSTART Submersible Level Generator Changeover Controller
MATelec Australia’s HydroSTART Submersible Level Generator Changeover Controller brings the features of the standard single and dual pump controllers into a new age with a redesigned capacitive touch keypad and control module with pump current sensing, providing wide range electronic overload protection which now functions with both single and three phase pumps.
Featuring a Generator Changeover switch to allow for a second supply to be brought in from a generator and the supply power transferred to the generator either manually or automatically.
Additional control inputs and functionality have been incorporated into the new design to enhance the controller’s flexibility and cover an even wider range of pumping applications. The HydroSTART is the new standard for pump controls.
Enclosure
- Powder coated mild steel enclosure with removable gland plate
- IP56 rated with inner door for outdoor mounting
Protection
- Pad-lockable mains power isolator switch
- Low voltage control and input circuitry
- Individual pump circuit breaker protection/isolation
- Contactors for pump switching (three-phase panels)
- Electronic short and overload protection of alarms
- Din rail mounted terminal connections
Control & Interface
- HydroSTART single or dual pump capacitive touch keypad interface:
- Indicator lights for system and pump status, level alarm
- Buttons for alarm mute/reset and pump mode selection
- HydroSTART PCB control module with dipswitches for adjusting configuration
- Visual (strobe) and audible (buzzer) alarms
- Pump current sensing providing adjustable overload & other protections
- ATS – Features Automatic Generator Supply changeover in the event of mains power failure
- GEN – Features a Manual Generator supply changeover switch.
Inputs
- Single phase (230Vac) or three phase (400Vac) Mains power supply
- Supply terminals for Single Phase (230Vac) or Three Phase (400Vac) Generator input power.
- 6x digital inputs for float or pressure switches, optional prime loss flow switch and system enable
- Standard terminal setup: Low level, duty stop, duty start, standby start, high level and system enable
Outputs
- 1 or 2x pump supply outputs
- BMS volt-free output for common fault
- Modbus RTU Serial RS485 connections for SCADA
Code | No of Pumps | Phase/Voltage | Selectable Overload Options | Doors |
FPC-82141-ATS | Single | 1 Phase / 230 Vac | 0.1-6AMP, 5-16AMP | 2 |
FPC-82143-ATS | Single | 3 Phase / 400 Vac | 0.1-6AMP, 5-16AMP | 2 |
FPC-82241-ATS | Dual | 1 Phase / 230 Vac | 0.1-6AMP, 5-16AMP | 2 |
FPC-82243-ATS | Dual | 3 Phase / 400 Vac | 0.1-6AMP, 5-16AMP | 2 |
FPC-82141-GEN | Single | 1 Phase / 230 Vac | 0.1-6AMP, 5-16AMP | 2 |
FPC-82143-GEN | Single | 3 Phase / 400 Vac | 0.1-6AMP, 5-16AMP | 2 |
FPC-82241-GEN | Dual | 1 Phase / 230 Vac | 0.1-6AMP, 5-16AMP | 2 |
FPC-82243-GEN | Dual | 3 Phase / 400 Vac | 0.1-6AMP, 5-16AMP | 2 |